4-33

Programming Reference

P.031 to P.038 Preset Speed 1 Through Preset Speed 8

(continued)

Each speed is selected using external switches connected to terminals 17, 18, and
19 on the Regulator board. The presets may also be selected using the Remote
Meter Interface (RMI) board. Refer to the RMI board instruction manual (D2-3341)
for more information.

Table 4.4 – Preset Speed Digital Inputs

Digital Inputs (Terminals)

7 (18)

0 (open)

0 (open)

1 (closed)

1 (closed)

0 (open)

0 (open)

1 (closed)

1 (closed)

6 (19)

0 (open)

1 (closed)

0 (open)

1 (closed)

0 (open)

1 (closed)

0 (open)

1 (closed)

8 (17)

0 (open)

0 (open)

0 (open)

0 (open)

1 (closed)

1 (closed)

1 (closed)

1 (closed)

Selected

Speed Reference

P.031 or analog input (see P.008,

selections 5, 6, and 7)

P.032

P.033

P.034

P.035

P.036

P.037

P.038

If you have installed an optional RMI board in your drive, refer to Appendix E for