U.006 magnetizing current, U.007 motor nameplate volts – Rockwell Automation GV3000/SE 230VAC 1-20 HP GP & Vector Drive Ver. 6.04 Software Start-Up and Ref. User Manual

Page 161

Advertising
background image

4-75

Programming Reference

Magnetizing Current = x 100

U.006 Magnetizing Current

This parameter
identifies the
percentage of
magnetizing current
(no load amps) with
respect to motor
rated amps.

A value is
automatically
generated for this
parameter when
self-tuning is
performed (U.008).

ATTENTION: If this parameter is set incorrectly, overcurrent or
excess heating of the motor could result. Failure to observe this
precaution could result in damage to, or destruction of, the equipment.

If the motor nameplate shows the no load current data, then this parameter value
can be calculated using the following formula. If this data does not appear on the
motor nameplate, perform the self-tuning procedure (U.008) to automatically
calculate the result.

No Load Amps
Motor Rated Amps

Parameter Range:

10.00 to 80.00%

Default Setting:

Power Module-dependent, see Appendix C

Parameter Type:

Configurable

Refer also to parameters: U.008

Torque Self-Tune Enable

!

U.007 Motor Nameplate Volts

This parameter
identifies motor rated
voltage as it appears
on the motor
nameplate.

Important: This parameter must be set prior to activating the torque control

self-tuning operation (U.008).

If you change this parameter after performing self-tuning using parameter U.008,
you must repeat the self-tuning procedure.

Parameter Range:

100 to 345 volts

Default Setting:

230

Parameter Type:

Configurable

Refer also to parameters: U.008 Torque Self-Tune Enable