GV3000/SE 230 VAC Drive, Software Reference Version 6.04

The adjustment range for current limit is:

U.006 (Magnetizing Current) to 150%.

VALUE ENTERED:

Step 5.21 Press the

¥

key to decrease current limit percent.

Note that changing current limit rating affects the maximum attainable
torque the motor can produce.

Step 5.22 Press the ENTER key to save the entered value.

After pressing ENTER, the same parameter
number is displayed. You can now move to
the next parameter.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

Step 6. Program the Second Menu Vector (U) Parameters

This step describes how to program the Vector (U) parameters that apply to vector
regulation only. You will not be adjusting any parameters for V/Hz regulation (H
parameters) in this procedure.

Step 6.1 Press the PROGRAM key to return to the main menu level.

The display will return to the First Menu
General (P) parameters.