Starting Up the Drive for Volts/Hertz Regulation

The adjustment range is:

0.5 Hz to the value set for P.004 (Maximum
Speed).

VALUE ENTERED:

Step 3.11 Press the ENTER key to display the default setting of P.003.

This shows that the default setting for
Minimum Speed is 5.0 Hz.

Step 3.12 Press the

£

key to increase minimum speed or the

¥

key to decrease

minimum speed.

Step 3.13 Press the ENTER key to save the changed value.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

After pressing ENTER, the same parameter
number is displayed. You can now go to the
next parameter.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

Step 3.14 Press the

£

key to display P.004, Maximum Speed.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

This parameter sets the maximum speed in
Hz.

In addition, the drive has overfrequency
protection by means of H.022. Refer to the
description of this parameter and be sure to
set it appropriate to your application.