Rated drive output amps – Rockwell Automation GV3000/SE 230VAC 1-20 HP GP & Vector Drive Ver. 6.04 Software Start-Up and Ref. User Manual

Page 23

Advertising
background image

1-9

Starting Up the Drive for Volts/Hertz Regulation

Use the following equation to calculate
current limit:

Motor Rated Amps

(1)

Rated Drive Output Amps

(2)

(1)

From motor nameplate

(2)

See the hardware reference manual for

ratings.

Adjustment Range: 50 to 110

VALUE ENTERED:

x 100

Step 3.18 Press the

£

key to display P.005, Current Limit.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

This parameter sets Current Limit, which
corresponds to the value in parameter
P.095, Power Module Output Amps.

Step 3.19 Press the ENTER key to display the default setting of P.005.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

This shows that the default setting for
Current Limit is 100.

Step 3.20 Press the

¥

key to decrease current limit. Decrease current limit only

if the motor nominal current rating is less than the drive nominal current
rating.