Step 7. Set the Motor Top Speed

This step sets the Motor Top Speed (U.017) in RPM. For applications that do not
support field weakening, Motor Top Speed must be equal to U.005 (Motor
Nameplate RPM). For applications that do support field weakening, Motor Top
Speed is the maximum field-weakened speed.

Step 7.1 Press the

¥

key until U.017 is displayed.

This parameter is the Motor Top Speed in
RPM.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

Step 7.2 Press the ENTER key to display the default setting of U.017.

This displays the default setting for the Motor
Top Speed. The actual setting depends on
the Power Module HP type. The display
shown here is only an example.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

Step 7.3

Check the value entered for Step 6.25 (U.005, Motor Nameplate RPM).
If the application does not support field weakening, U.005 and U.017
must be the same. If the application does support field weakening, the
value can be set higher. Press the

£

or

¥

key until the value is set

appropriately.

The adjustment range is:

The value set for U.005 to (Maximum value
depends on settings of U.002 and U.003)

VALUE ENTERED: