Starting Up the Drive for Vector Regulation

Step 10.8 Visually check that the motor rotates counter-clockwise (CCW) when

viewed from the driven motor shaft end.

CCW

Step 10.9

If the rotation direction is NOT correct, press the STOP/RESET key and
continue with Step 10.10.

If the rotation direction is correct, continue with Step 10.14.

AUTO

MAN

Forward
Reverse

PROGRAM

RUN
JOG

STOP

RESET

START

ENTER

SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password

RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM

When the STOP/RESET key is pressed, the
RUNNING LED turns off.

Step 10.10 Turn off and lock out or tag power to the drive.

Step 10.11 Verify that the DC bus capacitors are discharged. Refer to hardware

reference manual for this procedure.

Step 10.12 Switch any two of the motor leads (U, V, or W) and A and A NOT on

the encoder.

Step 10.13 Turn power on, and press the START key. Repeat Step 10.8.

Step 10.14 To make sure the drive is not inadvertently started, turn off and lock

out or tag power to the drive. Verify that the motor direction is
appropriate for the required machine direction, and then connect the
motor to the load.