F-1

Using the Terminal Strip Analog Input

An analog reference input is provided at terminals 12 through 15 on the drive's
Regulator board. This input accepts either a +/–10 VDC or 0 to 20 mA signal. The
analog-to-digital conversion provides 10-bit plus sign resolution and a digital range
of +/–1023.

The analog input can be used as a reference for:

Speed reference (P.000, P.007/P.008)

Trim reference (P.014)

Torque reference (vector control only) (U.000)

Outer control loop feedback (U.040)

Parameters P.009 (Terminal Strip Analog Input Offset) and P.010 (Terminal Strip
Analog Input Gain) are used to adjust the converted value for any external signal
errors. Parameter P.011 (Terminal Strip Analog Input Configure) is used to specify
the type of signal used and to invert the converted value, if required.

Three quantities are calculated from the analog input value: scaled, speed
normalized, and torque reference. The scaled value is used for the outer control
loop (OCL) feedback. The speed normalized value is used for either speed or trim
reference. The torque reference value is used for torque reference for vector
control. Figure F.1 shows the relationship between the input and the calculated
values.

A

PPENDIX

F

Using the Terminal Strip Analog Input

Figure F.1 – Terminal Strip Analog Input

Analog Input

(+/- 1023)

Loss

Detect

P.009

P.010

P.011

P.004

P.003

G

G

+

+

+

+

P.011

x4

x4

Analog Input Scaled

4095 @ 10V (20 mA)

Analog Input

Normalized to Speed

P.004 @ 10V (20 mA)

Analog Input Torque

Reference

150% iq @ 10V (20 mA)

Aln Alarm

Aln Fault