Precharge Staging

Parameter 472 [PreCharge Delay] can be used in conjunction with a precharge
enable (see condition one in Precharge Operation on

page 112

) to coordinate the

precharge operation of a group of drives. Typical uses may include common bus
or shared bus applications. The precharge coordination can be open loop, using
different precharge delay times or could be closed loop by monitoring the
precharge done status (parameter 555 [MC Status], bit 11 “PreChrg Done”) of
each drive before the next drive in the sequence is enabled for precharge. The
maximum value for [PreCharge Delay] is limited by parameter 410 [PreChrg
TimeOut]. The maximum value for [PreCharge Delay] is determined by the
following calculation:

• [PreCharge Delay] max = [PreChrg Timeout] - 1

Motor Sim Mode

When motor simulation mode is selected, the precharge requirements are
ignored and the precharge done condition is not required to run the drive.

External Power Supply

If the drive is used with an external power supply, the user should not request
precharge until the drive incoming power is available. If the user does request
precharge without incoming drive power, a precharge timeout fault will occur (if
configured for a fault).

Preset Speeds

There are seven preset speeds available for use. Refer to

Speed Reference on

page 145

for more information.