Detailed Drive Operation Chapter 1

half to the end of the ramp (as shown in the example below). The result of the S-
curve block can be seen in parameter 43 [Ramped Spd Ref ].

Speed Reference Bypass and Delayed Speed Reference

By default, parameter 37 [Spd Ref Bypass] is linked to parameter 43 [Ramped
Spd Ref ]. However, if you wish to bypass the rest of the speed reference control
loop, [Spd Ref Bypass] can be linked to other parameters.

Parameter 45 [Delayed Spd Ref ] is delayed by one scan of the speed control loop.
Parameter 37 [Spd Ref Bypass] can be linked to [Delayed Spd Ref ] instead of
[Ramped Spd Ref ] for use in SynchLink applications. See

SynchLink on

page 180

for more details.

Inertia Compensation

Inertia compensation is used to calculate the level of torque required due to load
inertia during speed changes. For more information on inertia compensation, see

Inertia Compensation on page 62

.

S Curve Time = 1.0 second

Speed

Time in Seconds

0.5 sec.

Accel Time = 5.0 seconds

Total Ramp Time = 6.0 seconds

0.5 sec.

37

43

45

Delayed Spd Ref

Link

Spd Ref Bypass

Ramped Spd Ref

Delay

One

Scan