Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Reference Manual User Manual
Page 198

198
Rockwell Automation Publication PFLEX-RM003E-EN-E - January 2011
Chapter 1 Detailed Drive Operation
• Set parameter 861 [BitSwap 1A Bit] = 1. This parameter sets the bit that
you would like to turn on in the result, and is set to bit 1 because we want
to use bit swap 1 to turn on bit 1 “Spd S Crv En” of parameter 151 [Logic
Command].
• Link parameter 862 [Bit Swap 1B Data] to parameter 824 [Local I/O
Status]. Parameter 862 [Bit Swap 1B Data] sets the data that you would
like to compare.
• Set parameter 863 [BitSwap 1B Bit] = 3. This parameter indicates that bit
3 of parameter 824 is used. Bit 3 of parameter 824 [Local I/O Status]
indicates that digital input 3 has turned on.
• Link parameter 151 [Logic Command] to parameter 864 [BitSwap 1
Result]. The result of bit swap 1 will control parameter 151.
The overall function of BitSwap 1 is that when digital input 3 turns on, we turn
on bit 1 “Spd S Crv En” of parameter 151 [Logic Command].
For another example using multiple bitswaps and the 16 position selector switch
to control the point to point position with digital inputs see
MOP
The motor operated potentiometer (MOP) allows you to increase and decrease a
DInt (double integer) or floating point value using two inputs. The inputs can
come from digital inputs, a network, or DriveLogix.
1087
1086
00
1086
01
1086
02
MOP
Rate
Increment
Decrement
Reset
Limit
1088
1089
1086
03
1086
04
1090
MOP High Limit
MOP Low Limit
1092
Convert
DInt-Real
x Scale
1091
MOP Scale DInt
MOP Rate
MOP Control
MOP Level Real
MOP Level DInt