Drivelogix, Drive overload, Drivelogix drive overload – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Reference Manual User Manual

Page 45: Theory of operation

Advertising
background image

Rockwell Automation Publication PFLEX-RM003E-EN-E - January 2011

45

Detailed Drive Operation Chapter 1

• During Flash mode, host stops ping, but still supports status/command

messages at a 1…5 second rate. drive will use 1 second rate. Data transfer
occurs via explicit message as fast as possible (i.e. peripheral request, host
response, peripheral request, etc.) but only between two devices.

The MUT, is based on the message type only. A standard command and Datalink
command could be transmitted from the same peripheral faster than the MUT
and still be O.K. However, two successive Datalink commands will have to be
separated by the MUT.

DriveLogix

See the

DriveLogix 5730 Controller User Manual, publication

20D-UM003

.

Drive Overload

Theory of Operation

The following discussion assumes that the IT curve does not change with Pulse
Width Modulated (PWM) carrier frequency or drive output frequency.

A drive has three rated current values; a continuous current rating, a 1 minute
current rating, and a 3 second current rating. Typically, the 1 minute rating will be
close to 110% of the continuous rating, and the 3 second rating will be close to
150% of the continuous rating. This may vary from drive to drive to optimize the
performance of each frame size. In the following examples the one minute rating
is 110% and the three second rating is 150%.

Open Loop Current Limit

The drive can thermally allow 102.5%.

The 1 minute current rating assumes a duty cycle of 1 minute on, followed by 3
minutes at 100%. This results in an average current of 102.5%.

The 3 second current rating assumes a duty cycle of 3 seconds on, followed by 57
seconds at 100%. This results in an average current of 102.5%.

Typically the drive will have a 60 second rating of 110% of continuous current
and a 3 second rating at 150% of the continuous current. Under normal operating
conditions, the open loop function sets this current limit to the short term (3
second) rating. If the function detects an overload, it lowers the limit to the
continuous level. If the function is in the continuous level limit, this can be lower

110% x 60 sec + 100% x 180 sec

average current = ------------------------------------------- = 102.5%

150% x 3 sec + 100% x 57 sec

average current = ------------------------------------------- = 102.5%

Advertising