Chapter 1, Detailed drive operation, Accel time – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Reference Manual User Manual

Page 13: Alarms, Accel time alarms, Chapter

Advertising
background image

Rockwell Automation Publication PFLEX-RM003E-EN-E - January 2011

13

Chapter

1

Detailed Drive Operation

This chapter explains PowerFlex 700S drive with Phase II control functions and
application programming in detail. Explanations are organized alphabetically by
topic. Refer to the Table of Contents for a listing of all topics in this chapter.

Accel Time

Parameter 32 [Accel Time 1] sets the rate at which the drive ramps up its output
after a Start command or during an increase in commanded speed (speed change).

The rate established is the result of the programmed acceleration time and the
programmed motor rated speed, set in parameter 4 [Motor NP RPM].

Times are adjustable in 0.0001 second increments from 0.01 to 6553.5 seconds.

Alarms

Alarms indicate conditions within the drive that could affect drive and
application operation. Alarms are selected during commissioning of the drive.
Examples of alarms include: encoder loss, communication loss or other
exceptions within the drive. A complete list of Alarms is included in the
Troubleshooting chapter of the

PowerFlex 700S AC Drive Phase II Control -

Programming Manual, publication

20D-PM001

.

ATTENTION: Only qualified personnel familiar with the PowerFlex
700S Drive and associated machinery should plan or implement the
installation, start-up and subsequent maintenance of the system. Failure
to comply may result in personal injury and/or equipment damage. See the
PowerFlex 700S AC Drive Phase II Control Frames 1…6 Installation
Instructions
, publication

20D-IN024

or the PowerFlex 700H and 700S

Frame 9…14 Drives Installation Manual, publication

PFLEX-IN006

, for

detailed drive installation information. See the PowerFlex 700S AC Drive
Phase II Control - Programming Manual
, publication

20D-PM001

, for

detailed drive start-up information.

Parameter 4 [Motor NP RPM]

Parameter 32 [Accel Time 1]

------------------------------------------------------------------------

Accel Rate

=

Advertising