Chapter 1 Detailed Drive Operation

Master PowerFlex 700S Drive Setup (Transmitting Drive)

1.

In the master, or transmitting drive, select the desired transmittal format in
the Transmit Format field. For this example, select “4 Direct Words, 8
Buffered Words.”

2.

Below the Transmit Format field, for Direct Word 0, do the following:
a. Click the arrow next to the Type field and select “Parameter.”

b. Click the

button to the right of the Source field and select 43

“Ramped Spd Ref.” This setting is to transmit the ramped speed from
the master.