Chapter 1 Detailed Drive Operation

To control from a communication network (20-COMM module):

1.

Toggle bit 1 “Start” in the logic command word on and then off to perform
a start.

2.

Toggle bit 9 “CoastStop” in the logic command word on and then off to
perform a coast stop.

To configure the drive for 3-wire control with a current limit stop:

For parameter 153 [Control Options], set bit 8 “3WireControl” = 1.

To control from digital inputs:

1.

Set one of the parameters 825…830 [Dig In

x Sel] = 18 “CurLim Stop.”

2.

Set a second parameter 825…830 [Dig In

x Sel] = 5 “Start.”

To control from a communication network (20-COMM module):

1.

Toggle bit 1 “Start” in the logic command word on and then off to perform
a start.

2.

Toggle bit 8 “CurrLimStop” in the logic command word on and then off to
perform a current limit stop.

Note:

In 3-wire mode, all stops commanded by pressing the HIM Stop button
are ramp stops.

Configuring the Start and Stop for 2-Wire Control (Maintained
Start and Stop)

To configure the drive for 2-wire control with a ramp stop:

Set parameter 153 [Control Options] bit 8 “3WireControl” = 0.

To control from digital inputs:

• Set one of the parameters 825-…830 [Dig Inx Sel] = 7 “Run”

To control from a communication network (20-COMM module):

1.

Turn on bit 1 “Start” in the logic command word to run.

2.

Turn off bit 1 “Start” in the logic command word to perform a ramp stop.