Chapter 1 Detailed Drive Operation

• Parameters 793 [Xsync In 3]…795 [Xsync Out 3 Dly] can be used to

synchronize a floating point parameter and delay it one scan.

• Parameter 787 [Xsync Gen Period] sets the scan time of the synch

generator. The following options are available:

The default setting is 1 = “1 ms.”

Task Time

Task times are adjustable for the 3 tasks in the drive.

• Task 1 includes the Speed Regulator, Speed/Position Feedback, Torque

Control, Current Control, Analog I/O and Digital I/O

• Task 2 includes the Speed Reference Control, Position Control and

Process PI Control

• Task 3 includes User Functions

The times are set by parameter 146 [FW TaskTime Sel] as listed below:

After changing the task time in parameter 146 [FW TaskTime Sel] a drive reset
must be performed (via the HIM navigate from the Main Menu to Diagnostics >
Faults > Reset Device) or drive power must be cycled before the change will be
active. Parameter 148 [FW TaskTime Actl] will then display the actual task time.

Test Points

Test points are used to monitor values in the drive for diagnostic information.

• [xxxx TP Sel] selects a value to monitor for diagnostics.

• [xxxx TP Data] shows the value selected by [xxxx TP Sel].

Thermal Regulator

Refer to

Drive Overload on page 45

.

0 = 0.5 ms
1 = 1 msec
2 = 2 msec
3 = 4 msec
4 = 8 msec

Parameter 146

Task 1 Time Task 2 Time Task 3 Time

0

0.5 ms

2 ms

8 ms

1

0.5 ms

1 ms

8 ms

2

0.25 ms

1 ms

8 ms