Chapter 1 Detailed Drive Operation

Speed Regulator Output Filter

Once the proportional and integrator blocks are summed, the torque reference
goes through a lead/lag filter, tuned by parameters 95 [SRegOut FiltGain] and 96
[SReg Out Filt BW]. For more information on lead/lag filters refer to

Lead-Lag

Filter on page 50

.

Parameter 157 [Logic Ctrl State] bit 8 “Spd Reg En” indicates when the speed
regulator is enabled. When bit 8 “Spd Reg En” is enabled, the speed regulator
output is allowed to pass to the torque control loop.

Parameter 302 [Spd Reg PI Out] contains the filtered, limited torque reference
that was generated by the speed regulator.

Speed Regulator Tuning

Basic Tuning with a Gear Box or Belt

This section provides guidelines for basic tuning of the speed loop when the
motor is coupled to the load through a gear box.

1.

Identify motor and system inertia (in seconds). The motor inertia can be
determined by performing an inertia test with the motor uncoupled from
the load, or the motor inertia in seconds can be calculated using the
following formula:

where WK

2

is the inertia in lbft

2

, RPM is the base motor speed of the

motor, and T

acc

is the rated torque of the motor in lbft. T

acc

can be

calculated using the following formula:

95

96

157

08

0

302

0

1

SRegOut FiltGain

SReg Out Filt BW

Logic Ctrl State

(Spd Reg En)

Spd Reg PI Out

to Torque Control

[4A1]

Lead Lag

(kn * s)+ wn