Rockwell Automation Publication PFLEX-RM003E-EN-E - January 2011

Chapter 1 Detailed Drive Operation

DInt to Real and Real to DInt Converters

The DInt to Real converter is used to convert a double integer parameter to a
floating point value. The resulting floating point value can then be linked to a
floating point parameter.

The Real to DInt converter is used to convert a floating point parameter to a
double integer value. The resulting double integer value can then be linked to a
floating point parameter.

Configuration:

• Parameter 1047 [DInt2Real1In] is the input value for DInt to Real value

conversion.

• Parameter 1048 [DInt2Real1 Scale] is the input value to scale the

conversion from DInt to Real. This is a multiplication to the input value
after conversion to a Real value.

• Parameter 1049 [DInt2Real1Result] is the resultant output of the

conversion form a DInt value to a Real value after scaling.

• Parameter 1050 [Real2DInt In] is the input value for Real to DInt value

conversion.

• Parameter 1051 [Real2DInt Scale] is the input value to scale the

conversion from Real to DInt. This is a multiplication to the input value
after conversion to a DInt value.

• Parameter 1052 [Real2DInt Result] is the resultant output of the

conversion form a Real value to a DInt value after scaling.

Convert

DInt-Real

x Scale

1049

1047

1048

Convert

Real-DInt

x Scale

1052

1050

1051

DInt2Real1 In

DInt2Real1 Scale

Real2DInt In

Real2DInt Scale

DInt2Real1 Result

Real2DInt Result