Voltage class, On-off delay timers – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Reference Manual User Manual

Page 211

Advertising
background image

Rockwell Automation Publication PFLEX-RM003E-EN-E - January 2011

211

Detailed Drive Operation Chapter 1

On-Off Delay Timers

This feature provides the ability to set two delay timers. Each timer can be set for
an On delay timer or Off delay timer. The On delay timer defines the delay time
between a False to True transition (condition appears) on the output condition
and the corresponding change in state of an input/output. The Off delay timer
defines the delay time between a True to False transition (condition disappears)
on the output condition and the corresponding change in the state of the digital
output. The user-defined on/off delay timer is enabled by setting bit 6 “Delay
Timer” of Par 1000 [UserFunct Enable].

Link a word to [DelTmr

x TrigData] to control the on or off delay timer. The bit

within the selected word that will control the delay timer is set by [DelTmr

x Trig

Bit]. A positive value set in [DelTmr

x TrigBit] selects an On delay timer and a

negative value selects an Off delay timer. The status of the user-defined on or off
delay timer is displayed in [DelayTimer

xStats].

Voltage Class

PowerFlex drives are sometimes referred to by voltage “class.” This class identifies
the general input voltage to the drive. This general voltage includes a range of
actual voltages. For example, a 400V class drive will have an input voltage range of
380…480VAC. While the hardware remains the same for each class, other
variables, such as factory defaults and power unit ratings will change. In most
cases, all drives within a voltage class can be reprogrammed to another drive in the
class by using parameter 403 [Voltage Class] to reset a drive to a different setup
within the voltage class range.

As an example, consider a 480V drive. This drive comes with factory default
values of 480V, 60 Hz with motor data defaulted for U.S. motors (Hp rated, 1750
rpm, etc.) By setting the [Voltage Class] parameter to “Low Voltage” (this
represents 400V in this case) the defaults are changed to 400V, 50 Hz settings
with motor data for European motors (kW rated, 1500 rpm, etc.).

Delay

Timer 1

1112

0
1
2

DelayTimer1Accum

Timer Enabled
Timer Timing
Timer Done

1111

DelayTimer1PrSet

DelTmr1 TrigData

DelTmr1 TrigBit

1110

1108

1109

DelayTimer1Stats

On

Delay

Off

Delay

Timer did not reach On

delay time

On

Delay

Timer did not reach Off

delay time

Off

Delay

Data

Status

Bit

Digital

Out

Bit

Advertising