Proportional gain – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Reference Manual User Manual

Page 156

Advertising
background image

156

Rockwell Automation Publication PFLEX-RM003E-EN-E - January 2011

Chapter 1 Detailed Drive Operation

However, it will exhibit some over-shoot and under-shoot. Increasing the value of
[SpdReg AntiBckup] decreases the over-shoot and under-shoot, which is
desirable where back-up cannot be tolerated. However, this tends to increase the
following error: This parameter has no affect on the drive's response to load
changes. The recommended setting is 0.1 to 0.5. The following is an example of
how the anti-backup affects the speed regulator’s response.

Proportional Gain

The filtered speed error (after the servo lock is added and the anti-backup is
subtracted) is sent to the proportional gain block. The proportional gain
determines how much of a speed error occurs during a load transient.

Parameter 81 [Spd Reg P Gain] sets the proportional gain of the speed regulator.
It's value is automatically calculated based on the bandwidth setting in parameter
90 [Spd Reg BW] and parameter 9 [Total Inertia]. Proportional gain may be
manually adjusted by setting [Spd Reg BW] to a value of zero. Units are (per unit
torque) / (per unit speed). For example, when parameter 81 [Spd Reg P Gain] is
20, the proportional gain block will output 20% motor rated torque for every 1%
error of motor rated speed.

The maximum value for Par 81 [Spd Reg P Gain] = Par 90 [Spd Reg BW] x Par 9
[Total Inertia].

Max. Speed Regulator
Bandwidth (Par 90)

Total Inertia (Par 9)

Max. Speed Regulator
Proportional Gain (Par 81)

475 (0.5 ms)

x

0.01

=

4.75

650 (0.25 ms)

x

0.01

=

6.50

30 (sensorless mode)

x

0.01

=

0.03

475 (0.5 ms)

x

2.0

=

950

650 (0.25 ms)

x

2.0

=

1300

30 (sensorless mode)

x

2.0

=

60

Advertising