208

Rockwell Automation Publication PFLEX-RM003E-EN-E - January 2011

Chapter 1 Detailed Drive Operation

• Parameter 1062 [Logic/Cmpr State], bits 0 “Logic 1 Rslt”, 1 “Logic 2 Rslt”

and 2 “Logic 3 Rslt” display the logical states of the Logic routine
(parameters 1063…1070). A value of 0 = False and 1 = True.

• Parameter 1063 [Logic 1A Data] selects the data word for the first input to

Logic Block 1. See parameter 1061 [Logic Config].

• Parameter 1064 [Logic 1A Bit] selects the bit of Par 1063 for the first

input to Logic Block 1. Note: To invert the selected input enter the desired
bit as negative. Use -32 to invert bit 0.

• Parameter 1065 [Logic 1B Data] selects the data word for the second input

to Logic Block 1. See parameter 1061 [Logic Config].

• Parameter 1066 [Logic 1B Bit] selects the bit of parameter 1065 [Logic 1B

Data] for the second input to Logic Block 1. Note: To invert the selected
input enter the desired bit as negative. Use -32 to invert bit 0.

• Parameter 1067 [Logic 2A Data] selects the data word for the first input to

Logic Block 2. See parameter 1061 [Logic Config].

• Parameter 1068 [Logic 2A Bit] selects the bit of parameter 1067 [Logic

2A Data] for the first input to Logic Block 2. Note: To invert the selected
input enter the desired bit as negative. Use -32 to invert bit 0.

• Parameter 1069 [Logic 2B Data] selects the data word for the second input

to Logic Block 2. See parameter 1061 [Logic Config].

• Parameter 1070 [Logic 2B Bit] selects the bit of parameter 1069 [Logic 2B

Data] for the second input to Logic Block 2. Note: To invert the selected
input enter the desired bit as negative. Use -32 to invert bit 0.