Digital outputs, Digital input status bits, Technical information – Rockwell Automation 20D PowerFlex 700S AC Drives with Phase II Control Reference Manual User Manual

Page 39: High speed digital inputs: standard digital inputs

Advertising
background image

Rockwell Automation Publication PFLEX-RM003E-EN-E - January 2011

39

Detailed Drive Operation Chapter 1

High Speed Digital Inputs:

Standard Digital Inputs:

Digital Input Status Bits

Parameter 824 [Local I/O Status] bits 1 through 6 give the status of the digital
inputs. When the bit in [Local I/O Status] associated with the digital input is on,
this means that the drive recognizes that the digital input is on. When the bit
associated with the digital input is off, this means that the drive recognizes that
the digital input is off.

Digital Outputs

Technical Information

There are three digital outputs total.

• Two Digital Outputs are 24V DC, Sourcing / Sinking, Open Collector

Type. Max Load -Internal Source = 150 mA, External = 750 mA

• The 3rd Output is a Relay, Form C, 24V DC / 120V AC, Max Load 2 A

DigIn Debounce

Debounce

SynchLink

Bit Filter

08

Prt0/1

RegisCnfg

824

01

Selector

09

10 11

823

01 02

03 04

05

825

Local I/O Status

[DigIn 1]

Dig In1 Sel

Debounce

DigIn Debounce

823

11 12

13 14

15

824

03

Selector

827

Local I /O Status

Dig In3 Sel

Advertising