Chapter 1 Detailed Drive Operation

Motor Overload

The overload capability applies to the rated speed range.

Normal Duty

After continuous operation at the rated output current, overload may be 110%
rated output current (I

L

) for 1 minute as long as it is followed by a period of load

less than the rated current so that the output current over the duty cycle does not
exceed the rated output current (I

L

).

Example:

If the duty cycle requires 110% rated output current for 1 minute of every 10
minutes, the remaining 9 minutes must be at approximately 98% rated current or
less to maintain output current less than 100%. If the requirement is 1 minute out
of 60 minutes, the remaining 59 minutes must be at approximately 99% rated
current or less.

Figure 17 - Illustration of I

L

Heavy Duty

After continuous operation at the rated output current, overload may be 150%
rated output current (I

H

) for 1 minute as long as it is followed by a period of load

less than the rated current so that the output current over the duty cycle does not
exceed the rated output current (I

H

).

Example:

If the duty cycle requires 150% rated output current for 1 minute of every 10
minutes, the remaining 9 minutes must be at approximately 92% rated current or
less to maintain output current less than 100%. If the requirement is 1 minute out

1 minute

9 minutes

1.1 x I

L

Time

Current

I

L