Rockwell Automation Publication PFLEX-RM003E-EN-E - January 2011

Chapter 1 Detailed Drive Operation

Figure 8 - Second Order Low Pass Filter

There is a second order low pass filter in the Speed Control-Regulator. This filter
is located after the speed error signal. The break frequency is set by parameter 89
[Spd Err Filt BW]. The break frequency is set to five times (5x) the Speed Loop
Bandwidth. This filter is used to attenuate any high frequency noise that the
speed loop would not be able to control.

Lead-Lag Filter

The PowerFlex 700S incorporates a generic lead-lag filter. The filter has the
following Laplace transfer function:

Kn is the gain term for the filter and Wn is the frequency term for the filter.

Lead-Lag Filter “lag”

When Kn is less than one (Kn<1) the filter behaves like a low pass filter.

Figure 9 on page 51

shows the lead-lag in a “lag configuration.” The unique aspect

of this filter is that the gain stops once the input frequency is equal to Wn/Kn.
Another aspect to this filter is that there is a mild phase shift during the
attenuation.

Bode Di

a

gr

a

m

M

a

gnit

u

de (dB)

Ph

as

e (deg)

Fre

qu

ency (r

a

d/

s

ec)

Fre

qu

ency

0

-10

-20

-

3

0

-40

-50

10

0

10

1

10

2

S

y

s

tem:

s

y

s

Fre

qu

ency (r

a

d/

s

ec): 9.

8

5

M

a

gnit

u

de (dB): -5.91

0

-45

-90

-1

3

5

-1

8

0

Kn

s

wn

+

×

s

wn

+

------------------------------

Advertising