Chapter 1 Detailed Drive Operation

Controlling the MOP from Digital Inputs:

Program one of the digital inputs, parameters 825 [Dig In1 Sel]…830 [Dig In6
Sel], to 23 “MOP Inc.” Turn on the digital input to increase the MOP level at the
rate programmed.

Program a second digital input, parameters 825 [Dig In1 Sel]…830 [Dig In6 Sel],
to 24 “MOP Dec.” Turn on the digital input to decrease the MOP level at the rate
programmed.

A digital input can also be programmed to 25 “MOP Reset.” Turning on this
digital input resets the MOP level to 0.

Controlling the MOP from a Network or DriveLogix

Turn on parameter 1086 [MOP Control], bit 0 “Increase” to increase the MOP
level at the rate programmed. Turn on parameter 1086 [MOP Control], bit 1
“Decrease” to decrease the MOP level at the rate programmed. Parameter 1086
[MOP Control], bit 2 “Reset” can be toggled to reset the MOP level.

Parameter 1086 can be controlled from a network by using a Datalink. Refer to

Datalinks on page 1-35

for details on using Datalinks.

Parameter 1086 can be controlled from DriveLogix by linking it to one of the
“FromDriveLogix” words (parameters 602…622). See the

DriveLogix 5730

Controller User Manual, publication

20D-UM003

, for more details on setting up

DriveLogix.

Selector Switches

There are three different selector switches available:

1.

A switch that selects up to 16 floating point values. The result is available
as a DInt (double integer) or floating point.

2.

A switch that selects between two floating point values. The result is
floating point.

3.

A switch that selects between two DInt values. The result is DInt.