Rockwell Automation Publication PFLEX-RM003E-EN-E - January 2011

Chapter 1 Detailed Drive Operation

Example Configuration 1:

This configuration sends the motor torque current reference value to a 0…10V
analog output signal.

• Parameter 831 [Anlg Out1 Sel] = 15 “Motor TrqRef ”

• Parameter 835 [Anlg Out1 Scale] = 0.1 per Volt

Motor torque is a per unit value where a value of 1 corresponds to 100% motor
torque. Therefore, parameter 831 [Anlg Out1 Scale] is set to 0.1 per 1V so that
when [Motor Torque Ref ] = 1 p.u., the analog output = 1 / 0.1 = 10V.

Example Configuration 2:

This configuration sends parameter 763 [Position Actual] out to a 0…10V analog
output signal.

• Parameter 831 [Anlg Out1 Sel] = 0 “User Select”

• Parameter 832 [Anlg Out1 DInt] is linked to parameter 763 [Position

Actual]

• Parameter 835 [Anlg Out1 Scale] is set to 214748364.7 per Volt

Parameter 763 [Position Actual] is an integer parameter with a range from
-2147483648 to +2147483647. Parameter 832 [Anlg Out1 DInt] is used
because parameter 763 [Position Actual] is an integer parameter.

Parameter 835 [Anlg Out1 Scale] is set to 214748364.7 per Volt so the analog
output will provide -10V when the position is -2147483647 and will +10V when
the position is +2147483647.

Auto/Manual

The Auto/Manual function on the LCD HIM is not functional on the
PowerFlex 700S drive with Phase II control.

Limit

10 [x]

X

1

[x]

833

834

835

836

D/A

12bit

837

Anlg Out1 DInt

Anlg Out1 Real

Anlg Out1 Scale

Anlg Out1 Zero

Anlg Out1 Value

TB1-09

TB1-10

+

-

832

Anlg Out1 Offset

+

+

+

+

821

16

Analog I/O Units

(AO1 Current)

Selector

Anlg Out1 Sel

831

Dflt = 18