Detailed Drive Operation Chapter 1

Position Output

Example:

A material handling application uses the PPMP to move the materials from one
position to another.

Turn on the position control and Motion Planner functions in the firmware:

• Set bits 16 “PositionCtrl” and 19 “MotinPlanner” of parameter 147 [FW

Functions En] = 1

The moves should be absolute:

• Set bit 0 “Absolute” of parameter 1134 [PPMP Control] = 1

The desired speed for the moves is 1000 rpm:

• Set parameter 1136 [PPMP Rev Spd Lim] = -1000 rpm
• Set parameter 1137 [PPMP Fwd Spd Lim] = 1000 rpm

The desired acceleration time to base motor speed is 0.5 s:

• Set parameter 1139 [PPMP Accel Time] = 0.5 s
• Set parameter 1140 [PPMP Decel Time] = 0.5 s

Enable the position loop:

• Set parameter 151 [Logic Command] bit 13 “Position En” = 1
• Set parameter 740 [Position Control] bit 1 “Speed Out En” = 1

Set up the position reference from the Motion Planner:

• Link parameter 743 [Aux Posit Ref ] to parameter 1143 [PPMP Pos

Output]

• Set parameter 742 [Position Ref Sel] = 1 “AuxPosit Ref ”

Set up the speed reference for the feed forward from the Motion Planner:

• Link parameter 10 [Speed Ref 1] to parameter 1142 [PPMP Spd Output]
• Set parameter 11 [Spd Ref1 Divide] = 1
• Set parameter 27 [Speed Ref A Sel] = 1 “Speed Ref 1”
• Set parameter 151 [Logic Command] bit 0 “SpdRmp Dsbl” = 1

To perform a move, set the position that you would like to move to in parameter
1130 [PPMP Pos Command] and then toggle parameter 1134 [PPMP Control]
bit 2 “Start”.