Detailed Drive Operation Chapter 1

Peak Detect

There are two peak detectors that can be used to detect the peak for a parameter
value.

Configuration:

• Link parameter 212 [PkDtct1 In DInt] or 213 [PkDtct1 In Real] to the

parameter for which you want to detect a peak value, depending on the
data type.

• To detect positive peak values, set parameter 210 [PeakDtct Ctrl In], bit 2

“Peak1SelHigh” = 1. To detect negative peak values, set parameter 210
[PeakDtct Ctrl In], bit 2 “Peak1SelHigh” = 0.

• The peak value is contained in parameter 215 [PeakDetect1 Out].

• To reset the output of the peak detector, toggle on then off parameter 210

[PeakDtct Ctrl In], bit 0 “Peak 1 Set”. The output will match the value in
parameter 214 [PeakDtct1 Preset], which is a default of 0.

• To hold the output of the peak detector at the present value, set parameter

210 [PeakDtct Ctrl In], bit 1 “Peak 1 Hold” = 1.

The change bit, parameter 211 [PeakDtct Status], bit 0 “Peak 1 Chng” is set to
“1” for one scan if the peak detect value changes, otherwise the change bit is set to
“0”. The change bit is also set to “0” if the detector is in Set or Hold mode.

214

212

213

210

2

PeakDtct Status
(Peak 1 Chng)

PkDtct1 In Real

PkDtct1 In DInt

PeakDtct Ctrl In
(Peak1SelHigh)

PeakDtct1 Preset

PeakDetect1 Out

PeakDtct Ctrl In

(Peak 1 Hold)

Σ

PeakDtct Ctrl In

(Peak 1 Set)

211

0

210

1

210

0

215

Peak Detect

218

216

217

210

6

PeakDtct Status
(Peak 2 Chng)

PkDtct2 In Real

PkDtct2 In DInt

PeakDtct Ctrl In
(Peak2SelHigh)

PeakDtct2 Preset

PeakDetect2 Out

PeakDtct Ctrl In

(Peak 2 Hold)

Σ

PeakDtct Ctrl In

(Peak 2 Set)

211

1

210

5

210

4

219

Peak Detect