Detailed Drive Operation Chapter 1

Nomenclature

Low Pass Filter

A low pass filter is designed to pass low frequencies and attenuate high
frequencies. The break point between high and low is called the cut off
frequency.

Figure 7 - Bode Plot Low Pass Filter (

ω

co

= 10 radians/second)

The Process Control Loop has a low pass filter immediately after the error signal.
The break frequency is set by parameter 184 [PI Lpass Filt BW]. The filter is used
to eliminate unwanted noise in the feedback. Typical range is between 10
radians/second to 50 radians/second.

Second Order Low Pass Filter

A second order low pass filter is similar to a low pass filter, however the
magnitude rolls off twice as fast as a first order low pass filter. Also the phase shift
of a second order filter is from 0 to 180° compared to 0 to 90° of a first order filter.