Rockwell Automation Publication PFLEX-RM003E-EN-E - January 2011

183

Detailed Drive Operation Chapter 1

• 25 “Opt0 Accum” - Use this selection to transmit feedback option 0

counts directly through before they enter the feedback control loop. This
eliminates the update delay of the feedback control loop.

• 26 “Opt1 Accum” - Use this selection to transmit feedback option 1

counts directly through before they enter the feedback control loop. This
eliminates the update delay of the feedback control loop.

Parameter 964 [Tx Dir Data Type] bits 0…3 select whether the direct data words
transmitted over SynchLink will be DInt (double integer) or real (floating point)
data. When the bit is turned off, it means the data transmitted will be DInt.
When the bit is turned on, it means the data transmitted will be floating point.
The default is all DInt words.

Figure 28 - Diagram of Direct Transmit Data (Word 00)

Multiply Block

SynchLink has the ability to take one of the direct data words and multiply it by a
constant or parameter value for features such as draw control. Parameters for the
multiply block must be setup in the Master as well as the Follower drive.

Parameter 927 [SL Mult State] contains overflow bits if the data for the multiply
block is too large. It contains the following bits:

0

1

911

SL Tx DirectSel0

2

3

10

21

22

23

24

25

26

965

SL Dir Data Tx00

929

SL Dir Data Rx00

Convert

Real-DInt

x Base

922

921

SL Real2Dint In

SL Mult Base

SL Real2Dint Out

923

From Encdr0 Accum

From Encdr1 Accum

From Fdbk Opt0 Accum

From Fdbk Opt1 Accum

0

SL Clr Events

916

230

Encdr0 Position

240

Encdr1 Position

250

FB Opt0 Posit

252

FB Opt1 Posit

From Registration Latch 0

From Registration Latch 1

235

RegisLtch0 Value

239

RegisLtch1 Value

SL Dir Tx Word 00

to SL Hardware

Tx Dir Data Type
(SLDir00 Real)

0

1

Convert

Real-DInt

00

964