Speed Reference Ramp

The speed reference ramp should be disabled when using the drive as a position
follower. To disable the speed reference ramp, set parameter 151 [Logic
Command], bit 0 “SpdRamp Dsbl” = 1.

Enabling the Position Loop

The firmware function for the position loop must be turned on by setting
parameter 147 [FW Functions En] bit 16 “PositionCtrl” = 1.

To enable the position loop, set parameter 151 [Logic Command], bit 13
“Position En” = 1.

Then to allow the output of the position loop to trim the speed set parameter 740
[Position Control], bit 1 “Speed Out En” = 1.

Position Reference Selection

For a position follower application set parameter 742 [Position Ref Sel] = 1
“AuxPosit Ref.” The auxiliary position reference is generally used for position
following applications.

Link parameter 743 [Aux Posit Ref ] to the position for the feedback device. For
example, to follow Encoder 1 link parameter 743 [Aux Posit Ref ] to parameter
240 [Encdr1 Position]. Encoder 1 position becomes the position reference for the
position loop.

0

1

749

743

742

Interp Position

Aux Posit Ref

2

758

Pt-Pt Posit Ref

Posit Ref Sel

Selected
Position
Reference