Detailed Drive Operation Chapter 1

Using Digital Inputs and the Selector Switches to Configure Preset Speeds:

The digital inputs can be used to configure up to 16 preset speeds using the
Selector Switches function.

Example Digital Input and Selector Switch Configuration:

In this example, three digital inputs are used to control the status of bits 1 “Sel
Swtch 00”…3 “Sel Swtch 02” of parameter 1022 [Sel Switch Ctrl] to then select
one of eight preset speeds configured in parameters 1029…1036. The binary
coded decimal (BCD) output of bits 1 “Sel Swtch 00”…3 “Sel Swtch 02” of
parameter 1022 are or’d together to select the desired parameter and preset speed.

• Set parameter 826 [Dig In2 Sel] to 34 “UserGen Sel0”. When digital input

2 is energized, bit 1 “Sel Swtch 00” of parameter 1022 is set high.

• Set parameter 827 [Dig In3 Sel] to 35 “UserGen Sel1”. When digital input

3 is energized, bit 2 “Sel Swtch 01” of parameter 1022 is set high.

• Set parameter 828 [Dig In4 Sel] to 36 “UserGen Sel2”. When digital input

2 is energized, bit 3 “Sel Swtch 02” of parameter 1022 is set high.

• Set bit 1 “Sel Switches” of Par 1000 [UserFunct Enable] to “1” (enables the

Selector Switch user function).

• Set bit 0 “SSW DataPass” of Par 1022 [Sel Switch Ctrl] to “1” (enables the

passing of the data from the selected parameter to Par 1045 [SelSwtch
RealOut] and 1046 [SelSwtch DIntOut]).

1029

1030

1031

0

1

2

3

4

5

6

1032

1034

1035

SelSwtch In01

(Real)

7

8

9

10

1036

1037

1038

1039

1040

12

13

14

15

11

1033

1041

1042

1043

1044

1045

1046

SelSwtch DIntOut

(Integer )

SelSwtch RealOut

(Real)

SelSwtch In02

(Real)

SelSwtch In03

(Real)

SelSwtch In04

(Real)

SelSwtch In05

(Real)

SelSwtch In06

(Real)

SelSwtch In07

(Real)

SelSwtch In08

(Real)

SelSwtch In09

(Real)

SelSwtch In10

(Real)

SelSwtch In11

(Real)

SelSwtch In12

(Real)

SelSwtch In13

(Real)

SelSwtch In14

(Real)

SelSwtch In15

(Real)

SelSwtch In00

(Real)

with Rounding

1022

00

Sel Swtch Ctrl

Binary Coded

Decimal (BCD)

control that selects

1 of 16 inputs (Pars

1029 – 1044 ) that

provides output to

Par 1045 or Par

1046 . BCD values

of bits 01 – 04 of

Par 1022 are or’d

together to select a

switch. Bit 01 of

1022 is the LSB. A

binary value of

“0000 ” selects Par

1029 . A binary

value of “1111 "

selects Par 1044 .

1022

02

03

Sel Swtch Ctrl

828

Dig In4 Sel

827

Dig In3 Sel

826

Dig In2 Sel

“UserGen Sel0”

“Sel Switch 00”

“Sel Switch 01”

“Sel Switch 02”

01

“UserGen Sel 1”

“UserGen Sel2”

825

Dig In1 Sel

829

Dig In5 Sel

830

Dig In6 Sel

04

“Sel Switch 03”

“UserGen Sel3”