Rockwell Automation Publication PFLEX-RM003E-EN-E - January 2011

179

Detailed Drive Operation Chapter 1

To configure the drive for 2-wire control with a coast stop:

Set parameter 153 [Control Options] bit 8 “3WireControl” = 0.

To control from digital inputs:

• Set one of the parameters 825…830 [Dig Inx Sel] = 7 “Run”

To control from a communication network (20-COMM module):

1.

Turn on bit 1 “Start” in the logic command word to run.

2.

Toggle bit 9 “CoastStop” in the logic command word on and then off to
perform a coast stop. Bit 1 “Start” in the logic command word must be
turned off and back on to run again (therefore, technically, there is no 2-
Wire control with a coast stop on a network because two bits must be
controlled).

To configure the drive for 2-wire control with a current limit stop:

Set parameter 153 [Control Options] bit 8 “3WireControl” = 0.

To control from digital inputs:

• Set one of the parameters 825…830 [Dig Inx Sel] = 7 “Run”

To control from a communication network (20-COMM module):

1.

Turn on bit 1 “Start” in the logic command word to run.

2.

Toggle bit 8 “CurrLimStop” in the logic command word on and then off to
perform a current limit stop. Bit 1 “Start” in the logic command word must
be turned off and back on to run again (therefore, technically, there is no 2-
Wire control with a coast stop on a network because two bits must be
controlled).

Note:

In 2 wire mode (parameter 153 [Control Options] bit 8
“3WireControl” = 0), the HIM Start button is not functional.

Start-Up

Refer to

Autotune - Start-Up Menu on page 1-19

for Start-Up information.

Stop Modes

Refer to

Start and Stop Modes on page 1-176

.