Detailed Drive Operation Chapter 1

Parameters 804, 810, and 816 [Al

x Filt Gain] and parameters 805, 811, and 817

[Anlg In

x Filt BW] are used to filter the analog input data. Refer to

Lead-Lag

Filter on page 50

for detailed information.

Configuration Example

This example illustrates how to setup a speed reference to follow a 0…10V analog
input signal and null out a small amount of offset from the A/D converter on the
analog input.

• Parameter 803 [Anlg ln1 Offset] = -0.0144V

• Parameter 802 [Anlg ln1 Scale] = 0.1 per 1V

• Parameter 804 [Al 1 Filt Gain] = 1

• Parameter 805 [Anlg ln1 Filt BW] = 0

• Parameter 10 [Speed Ref 1] is linked to parameter 800 [Anlg ln1 Data]

With a desired parameter 801 [Anlg In1 Value] of 0V, the drive was reading
0.0144V. To null out analog input 1, parameter 803 [Anlg In1 Offset] was set to -
0.0144V.

Parameter 10 [Speed Ref 1] is a per unit parameter, meaning that a value of 1
equates to base motor RPM. Therefore, to scale parameter 800 [Anlg In1 Data]
to give us a value from 0 to 1 for a 0…10V signal, parameter 802 [Anlg In1 Scale]
was set to 0.1 per 1V.

Parameter 805 [Anlg In1 Filt BW] was set to 0 so that no filtering took place on
analog input 1.

A/D

14bit

803

804

805

800

X

802

801

Anlg In1 Offset

Anlg In1 Scale

Anlg In1 Value

Anlg In1 Data

AI 1 Filt Gain

Anlg In1 Filt BW

TB1-01

TB1-02

+

-

Lead Lag

(kn * s)+ wn

s + wn

+

+

821

00

Analog I/O Units

(AI1 Current)