Rockwell Automation Publication PFLEX-RM003E-EN-E - January 2011

51

Detailed Drive Operation Chapter 1

Figure 9 - Kn < 1 “Lag Filter”

Figure 10

below shows the bode plot of the lag configuration. Kn is set to 0.7 and

Wn is set to 35 radians/second. The time domain shows a 100 radians/second
sinusoidal input. Notice that the phase shift between input and output are
marginal.

Figure 10 - Bode Plot and Time Domain of Lag

The lag configuration is good for eliminating unwanted noise and disturbance
such as backlash. There are two lead-lag blocks used in the speed regulator loop.
One is in the forward path and the other is in the feedback path.

For moderate filtering:

• Set Kn=0.7, Wn=0.35
• For Heavy filtering:
• Set Kn=0.5, Wn=20

Both the Forward and Feedback filters can be set to the same value to increase
their effectiveness.

Kn

Wn

Forward Path

Parameter 95 [SRegOut FiltGain]

Parameter 96 [SReg Out Filt BW]

Feedback Path

Parameter 93 [SRegFB Filt Gain]

Parameter 94 [SReg FB Filt BW]

g

a

in

1

kn

wn

kn

wn

“L

a

g

(kn <1)

w (r

a

d/

s

ec)