Detailed Drive Operation Chapter 1

Reset SynchLink

After setting up the configuration SynchLink must be reset on both drives in one
of the following ways:

• Set parameter 904 [SL Node Cnfg], bit 3 “Reset SL” = 1 on the drives.

This bit will automatically transition back to 0 after SynchLink is reset.
OR

• Perform a reset on the drives. This can be done via the HIM by navigating

from the Main Menu to Diagnostics > Faults > Reset Device.
OR

• Cycle power on the drives.

Sync Generator

The sync generator can be used to synchronize a parameter and delay it one scan.
This can be used in conjunction with SynchLink (Refer to

SynchLink on

page 180

for more information).

Configuration

• Parameters 788 [Xsync In 1] and 789 [Xsync Out 1] can be used to

synchronize a DInt parameter.

• Parameters 790 [Xsync In 2] through 792 [Xsync Out 2 Dly] can be used

to synchronize a DInt parameter and delay it one scan.

Latch

Latch

Latch

788

790

793

Sync Generator

787

789

791

792

794

795

317

0.5ms

Xsync In 1

Xsync Out 1

Xsync Out 2

Xsync In 2

Xsync In 3

Xsync Out 2 Dly

Xsync Out 3 Dly

Xsync Out 3

SL System Time

Sync Pulse Generator

0.5ms * 2

(p787)

0.5ms

786

00

Delay

One

Scan

Delay

One

Scan

Xsync Gen Period

Xsync Status
(Sync Pulse)