Chapter 1 Detailed Drive Operation

FIR Filter

The recommended setting for the FIR filter is eight taps when parameter 146
[FW TaskTime Sel] is set to 0 or 1 (0.5ms for task 1). When parameter 146 [FW
TaskTime Sel] is set to 2 (0.25 ms for task 1) the recommended setting for the
FIR filter is 16 taps. This sets the noise bandwidth for 120 radians/second. The
recommended setting reduces the effect of noisy feedback on the system, but
values above 120 radians/second for the speed regulator bandwidth may not be
effective.

In some cases, it may be desirable to increase the noise bandwidth in order to
allow a speed regulator bandwidth higher than 120 radians/second. The setting
of the FIR filter and parameter 89 [Spd Err Filt BW] can be changed to achieve a
higher noise bandwidth according to the following tables:

FIR and P89 [Spd Err Filt BW] Settings when P146 [FW TaskTime Sel] = 0 or 1:

FIR and P89 [Spd Err Filt BW] Settings when P146 [FW TaskTime Sel] = 2:

Sensorless

Sensorless mode is used when zero speed or more than a 120:1 speed range is not
required.

Parameter 226 [Motor Speed Est] contains the estimated motor speed, used
when sensorless mode is selected. The estimated speed feedback is based on
voltage feedback from the motor.

Parameter 227 [Motor Posit Est] is an estimated position for sensorless mode. It
is calculated based on parameter 226 [Motor Speed Est] and the value in
parameter 225 [Virtual Edge/Rev]. [Virtual Edge/Rev] is a user-defined value
for the number of pulses per motor revolution.

FIR filter setting (taps)

1

2

4

8

16

32

64

127

Spd Err Filt BW (rad/sec)

2000

1500

1300

600

300

150

75

38

Noise bandwidth (rad/sec)

400

300

220

120

60

30

18

8

FIR filter setting (taps)

1

2

4

8

16

32

64

127

Spd Err Filt BW (rad/sec)

4100

3200

2200

1300

600

300

150

75

Noise bandwidth (rad/sec)

690

530

380

240

120

60

30

15

227

225

Virtual Edge/Rev

Motor Posit Est

to Feedback
Selection

226

Accum

1

1-Z

-1

Motor Speed Est