Detailed Drive Operation Chapter 1

Speed Reference Filter

A lead-lag filter for the selected speed reference can be turned on by setting
parameter 153 [Control Options] bit 1 “SRef LdLg En” = “1”. Parameter 35
[SpdRef Filt Gain] sets the gain for the filter and parameter 36 [SpdRef Filt BW]
sets the bandwidth for the filter. For more information on lead/lag filters see

Lead-Lag Filter on page 50

.

Speed Reference Scaling

The speed reference value up to this point is multiplied by the scaling parameter
38 [Speed Ref Scale]. [Speed Ref Scale] is applied to all of the selected speed
references, as opposed to the specific scaling parameters for speed reference 1 and
2. [Speed Ref Scale] is a linkable parameter. This allows the speed reference value
to be scaled “dynamically” with an input signal if desired. An example would be
to have an analog input linked to the scale parameter. The speed reference and the
scale would then affect the value sent to the speed regulator.

Speed Trim 1

At this point in the speed reference control loop, parameter 21 [Speed Trim 1] is
added to the speed reference. [Speed Trim 1] can be used as a trim to the speed
reference. For example, [Speed Trim 1] can be linked to parameter 180 [PI
Output], which is the output of the Process PI loop. The resulting parameter 47
[SpdRef + SpdTrm1] is sent into the speed regulator loop.

153

01

35

36

From Ramp

To Speed
Reference Scale

Control Options

(SRef Filt En)

SpdRef Filt Gain

SpdRef Filt BW

Lead Lag

(kn * s)+ wn

s + wn

X

38

46

Scaled Spd Ref

Speed Ref Scale

to Speed Trim

from Speed

Ref Filter

21

47

46

Scaled Spd Ref

from Speed

Ref Scale

SpdRef + SpdTrm1

to Speed
Regulator

Speed Trim 1

+

+