KEYENCE IG Series User Manual

Page 56

Advertising
background image

3-8 Bank Function (Registering Multiple Tolerance Setting Values)

3-20

3

B

as
ic Oper

a

tion

s

IG-E

Switching the bank by the external input

When the Bank A input and Bank B input are set for the external inputs, the bank can be
switched using the external inputs.

"11. External input" (page 4-33)

1

Set the key lock function.

If you switch the bank by the external input, the sensor amplifier must be in a key
locked state.

"3-9 Key Lock Function" (page 3-21)

2

By combining ON/OFF setting of bank A input and bank B input, you can

switch the banks.

• The bank input must be held 20 ms or longer.

"11. External input" (page 4-33)

• The combinations of bank A input and bank B input are shown in the following

table.

Bank

Bank A input

Bank B input

Bank 0

OFF

OFF

Bank 1

ON

OFF

Bank 2

OFF

ON

ON : Short-

circuited

Bank 3

ON

ON

OFF: Open

Reference

If the external input is not set to bank A or bank B, it is regarded as OFF.
(example) If only Bank A input is set for the external input, only two patterns

(bank 0 and bank 1) can be switched using the external input.