RECORD

The RECORD command enables or disables the recording of bus data. RECORD

ON

causes the Analyzer488 to begin recording bus events into the record memory.

RECORD OFF

stops recording bus events.

There is an interaction between the RECORD and the SET TRIGGER

commands. If Triggering is disabled (by issuing the SET TRIGGER OFF command),
recording will begin upon receipt of the RECORD ON command and will stop upon
receipt of the RECORD OFF command.

If Triggering is enabled (by issuing the SET TRIGGER ON command),

recording will begin upon receipt of the RECORD ON command. If WHEN
COMPLETE STOP

is selected, recording will stop when match count occurrences

of match have occurred, trig delay events have occurred, and post count
events have occurred.

If WHEN COMPLETE STEP is selected, recording will remain on until the

RECORD OFF

command is received. Each time the STEP command is sent, the post

count

value returned by the STATUS 4 and STATUS 5 commands will be

incremented.

The query option, RECORD?, returns the string, RECORD ON, if record is

enabled or RECORD OFF if recording is disabled.

TYPE

Record command

SYNTAX

RECORD {[?]|[ON|OFF]}

RESPONSE

None

MODE

Any

BUS STATES

None

QUERY

RECORD ON

if record is enabled or RECORD OFF if record is

RESPONSE

disabled.