4 alarms and events, Shown in figure 7-3 – GE Industrial Solutions Entellisys 5.0 User Manual User Manual

Page 117

Advertising
background image

Bus Differential Relay

117

7

Figure 7-3 Bus differential user settings

7.1.1.4 Alarms and Events

Bus Differential Alarm and Trip functions have a configurable alarm for each zone. To configure
a Bus Differential alarm on the HMI:

1. On the Main Menu, click User Settings, and then select Alarms.
2. On the Alarms screen, click Alarms Setup as shown in Figure 7-4.
3. Select the Bus Differential Alarm or Trip Alarm and enter a comment in the Comment text

box.