System architecture

20

1

Test Connector
Connection point between the Entellisys System Test Kit and the Messenger.

Figure 1-8 EntelliGuard Messenger

The Messenger is located directly above the circuit breaker compartment.

1.3.5.2 Active Health Monitoring

The Entellisys Messenger actively monitors critical internal circuits which is displayed on the HMI
in the System Health screen. The HMI can also annunciate alarms on the following circuits:

• Communications channels A and B
• Control Power channels A and B
• Ibutton health
• Flux Shifter circuitry

Alarm Annunciation
User configured alarms can be configured at the HMI to annunciate locally, send
auto-generated email or programmed to energize an annunciator light (discrete I/O required).
(see

Alarms on page 215

).

The Messenger health alarms that can be configured are:

Flux Shifter Alarm

Messengers with hardware revision 5 and beyond, have a monitoring circuit which monitors the
Flux Shifter circuitry to ensure that it is armed and capable of tripping the breaker.

NOTE: This circuitry does not monitor the Flux Shifter coil or the electrical/mechanical
connections between the Messenger and the coil.

Compartment ID Button Missing

Indicates that the compartment ID button is either missing, damaged or not installed correctly.
(See

Compartment ID button on page 21

).

Messenger Communication Lost

Each Messenger has redundant ethernet channels (ethernet channels 1 and 2). This alarm
indicates that either comm 1, comm 2 or both channels have stopped communicating to the
default CPU.

Redundant CPU Messenger Comm Lost

Similar to the Messenger Communication Lost alarm above except it monitors the comm on the
redundant CPU.