GE Industrial Solutions Entellisys 5.0 User Manual User Manual

Page 202

Advertising
background image

FlexLogic™

192

11

ELEMENT:
Under frequency

UNDERFREQUENCY 1 ALARM PKP
UNDERFREQUENCY 1 ALARM OP
UNDERFREQUENCY 1 ALARM DPO

UNDERFREQUENCY 1 TRIP PKP
UNDERFREQUENCY 1 TRIP OP

UNDERFREQUENCY 1 TRIP DPO

Underfrequency 1 alarm function in pickup
Underfrequency 1 alarm activated
Underfrequency 1 alarm function not in
pickup
Underfrequency 1 trip function in pickup
Underfrequency 1 relay function tripped
breaker
Underfrequency 1 trip function not in pickup

UNDERFREQUENCY 2…30

Same set of operands as shown for
UNDERFREQUENCY 1

ELEMENT:
Undervoltage

UNDERVOLTAGE 1 ALARM PKP
UNDERVOLTAGE 1 ALARM OP
UNDERVOLTAGE 1 ALARM DPO
UNDERVOLTAGE 1 TRIP PKP
UNDERVOLTAGE 1 TRIP OP

UNDERVOLTAGE 1 TRIP DPO

Undervoltage 1 alarm function in pickup
Undervoltage 1 alarm activated
Undervoltage 1 alarm function not in pickup
Undervoltage 1 trip function in pickup
Undervoltage 1 relay function tripped
breaker
Undervoltage 1 trip function not in pickup

UNDERVOLTAGE 2…30

Same set of operands as shown for
UNDERVOLTAGE 1

FIXED OPERANDS

Off

On

Logic = 0. Does nothing and may be used as
a delimiter in an equation list; used as
'Disable' by other features.
Logic = 1. Can be used as a test setting.

INPUTS/OUTPUTS:
Contact Inputs

(Note: total contact
inputs + total contact
outputs <= 128)

Contact Input 1 On

Contact Input 128 On

Contact Input 1 Off

Contact Input 128 Off

External contact input 1 activated

External contact input 128 activated

External contact input 1 deactivated

External contact input 128 deactivated

INPUTS/OUTPUTS:
Virtual Inputs

Virtual Input 1 On

Virtual Input 32 On

Flag is set, logic = 1

Flag is set, logic = 1

INPUTS/OUTPUTS:
PLC Inputs

PLC Input 1

PLC Input 256

Flag is set, logic = 1

Flag is set, logic = 1

Table 11-2 Entellisys FlexLogic operands