A.2.5 CPU Status Events

Table A-6 CPU Status Events

Event

Description

Notes and Troubleshooting tips

Power On

CPU has powered on

Discrete IO Test Mode Initiated

Test mode for discrete I/O has been initiated

Discrete IO Test Mode Ended

Test mode for discrete I/O has ended

All Metering and Protection
Disabled

CPU is not performing any metering or protection,
either because it does not have a valid option string
or the firmware download is invalid

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention Invalid PT Rating Volts
Suspended

Programmed PT rating is not valid, no voltage
relays or metering will be done for Messengers that
use that Messenger as a voltage source

Contact GE Post Sales Service (see

How to

contact us on page 2

).

CPU Synch Clock Calibration OK Periodicity of CPU Synch Clock is within spec limits

Caution CPU Synch Clock Error
Backup Clock On

CPU cannot use CPU Synch Clock (Synch Clock is
missing or calibration failed) and is running from
the software backup clock

Verify that CPU Synch Clock is present and
powered. If it is, contact GE Post Sales Service
(see

How to contact us on page 2

).

CPU Synch Clock OK

CPU is running from the CPU Synch Clock

CPU Synch Clock Freq Mismatch CPU Synch Clock is interrupting at 50 Hz and CPU is

programmed for 60 Hz, or vice versa

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Waveform Capture Ignored
Check Messngr Status

All Messengers either decommissioned or are not
communicating, so no waveform data was
captured

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Waveform Capture Ignored
Buffer Protection On

Waveform buffer is full and write protection is on,
so waveform was not captured.

Clear waveforms, or allow Automatic
Overwrite of waveforms.

Waveform Capture Triggered By
FlexLogic

Logged when FlexLogic triggers a waveform
capture

Note Ethernet Err Port1 Receive
Invalid Frame

CPU received an invalid frame on Ethernet port 1
(e.g., invalid MAC address or size, invalid data size)

Verify that no devices other than the
Messengers and CPU are plugged into the
switch that connects the Messengers and
CPU.

Note Ethernet Err Port1 Receive CPU detected an error on ethernet port 1

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Note Ethernet Err Port1 Send

CPU failed to send an Ethernet packet from port 1.

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Note Ethernet Err Port1 Send
Restart

CPU restarted Ethernet port 1 transmit-driver.

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Note Ethernet Err Port1 Send
Queue Full

CPU failed to send an Ethernet packet from port 1
because Ethernet driver transmit-buffer is full.

Contact GE Post Sales Service (see

How to

contact us on page 2

).