4.8.3 Events and Alarm

Events

The Demand Alarm Function generates the following events:

• Alarm Pickup Over-Demand Flex X: Logged when demand metering alarm goes into

Over-Demand pickup state

• Alarm Over-Demand Flex X: Logged when demand metering over-demand alarm

operates. Also available as in the HMI Alarm screen.

• Alarm Dropout Over-Demand Flex X: Logged when demand metering alarm drops out

from over-demand pickup

• Alarm Pickup Under-Demand Flex X: Logged when demand metering alarm goes into

Under-Demand pickup state

• Alarm Under-Demand Flex X: Logged when demand metering under-demand alarm

operates. Also available as in the HMI Alarm screen.

• Alarm Dropout Under-Demand Flex X: Logged when demand metering alarm drops out

from under-demand pickup

4.9 Troubleshooting

Current reads zero or dashes

Verify that the Messenger is communicating to the CPU in the System Health screen. See

Monitoring system health on page 221

for more information.

Verify that the frame and CT ratings are properly configured. This information is available on
the Metering & Waveforms menu. See

Basic configuration on page 43

.

Verify the current exceeds 1% of CT rating. The system will zero the current if below 1%. To
verify this, trigger a waveform manually. The actual current will be displayed on the
waveform.

Voltage reads zero

Verify that the circuit breaker has a source for voltage data and that the source has a valid
PT assigned to it by clicking Metering on the Metering & Waveforms screen. See

Basic

configuration on page 43

. Also see

PT Throw-Over on page 125

for more information.

Detailed, Demand, or Harmonics metering buttons are grayed out

Verify that the corresponding option has been assigned to that circuit breaker. See

Options

on page 44

.