Single-point functions

92

5

system has located the responsible feeder. There are also several alarms to help alert the user.
(See

Events and Alarms on page 97

)

Operational limitations

Location may not find the faulted feeder under the following conditions:

• Load Currents above 1X (Overload)
• High Z fault (insufficient pulse current)
• Multiple feeders faulted
• Other rapid transient currents (i.e. motors starting every fraction of a second)
• Network (parallel) applications may not locate for mains and ties
• Minimum pulse current not met
• Breaker is in a reverse power condition

Figure 5-13 HRGF Detection and Location process - w/ optional trip enabled

5.3.2.1 Hardware Requirements

The system must be a High Resistance grounded system with HRGF detection and have either
redundant or non-redundant discrete I/O