Alarms and events

280

A

HRGF Location - Detection Not
Optioned Function 1-4

Logged when breaker that location function 1 is
associated with does not have HRGF optioned.

HRGF Location Incomplete
Missing Data Function 1-4

This event is logged when some messengers are
either decommissioned or non-communicating or
not-synched.

Relays – Synch Check

Synch Check Control Enabled
1…12

Synch check relay 1…12 has been enabled

Synch Check Control Disabled
1…12

Synch check relay 1…12 has been disabled

Synch Check 1…12 Sources Not
Synchronized

Messengers that are providing voltage information
for synch check relay are not synchronized, so the
CPU is unable to check for synchronization
between voltage sources.

This should only happen on start-up, or when
a Messenger is connected to the system (or
rebooted). If it happens repeatedly during
normal operation, contact GE Post Sales
Service (see

How to contact us on page 2

).

Synch Check 1…12 Sources Not
Compatible

Voltage sources for synch check relay 1…12 are not
compatible; i.e., they have different PT
configurations or ratings

Verify that the Source Voltages for the
synch check relay are correct.

Verify that the source voltages have the
correct PT configurations.

Synch Check 1…12 Dead Source
Operate

Dead source criteria for synch check relay 1…12
have been met

Synch Check 1…12 Dead Source
Drop Out

Dead source criteria for synch check relay 1…12
have been met

Synch Check 1…12 V1 Above
Minimum

Voltage source 1 for synch check relay 1…12 is
above the live source threshold

Synch Check 1…12 V1 Below
Maximum

Voltage source 1 for synch check relay 1…12 is
below the dead source threshold

Synch Check 1…12 V2 Above
Minimum

Voltage source 2 for synch check relay 1…12 is
above the live source threshold

Synch Check 1…12 V2 Below
Maximum

Voltage source 2 for synch check relay 1…12 is
below the dead source threshold

Overcurrent (including GF)

Pickup ST Overcurrent

Short time overcurrent function has entered pickup

Dropout ST Overcurrent

Short time overcurrent function has dropped out of
pickup

Breaker Trip ST Overcurrent

Breaker tripped due to short time overcurrent
condition

Pickup LT Overcurrent

Long time overcurrent function has entered pickup

Table A-9 Protection Relay Events

Event

Description

Notes and Troubleshooting tips