2 troubleshooting – GE Industrial Solutions Entellisys 5.0 User Manual User Manual
Page 118
Advertising
Multi-point functions
118
7
Figure 7-4 Bus differential alarms setup
Events
To view a table of the events generated by the Bus Differential Relay, see
7.1.2 Troubleshooting
Bus Differential Setting Change Rejected events are observed in the Sequence of Events log
•
Verify that the pickup setting is within the valid range. Valid range is from “Zone Minimum
Pickup” to 22,000 Amps. (See
Setting Bus Differential pickups/delays on page 116
Frequent suspended/resumed events are seen
•
Verify that both CPUs are operating with the hardware clock. This can be done from the
System Health screen. The Synchronization hardware OK indicator lights should be green for
both CPUs.