2 troubleshooting – GE Industrial Solutions Entellisys 5.0 User Manual User Manual

Page 118

Advertising
background image

Multi-point functions

118

7

Figure 7-4 Bus differential alarms setup

Events

To view a table of the events generated by the Bus Differential Relay, see

Bus Differential Events

on page 275

.

7.1.2 Troubleshooting

Bus Differential Setting Change Rejected events are observed in the Sequence of Events log

Verify that the pickup setting is within the valid range. Valid range is from “Zone Minimum
Pickup” to 22,000 Amps. (See

Setting Bus Differential pickups/delays on page 116

.)

Frequent suspended/resumed events are seen

Verify that both CPUs are operating with the hardware clock. This can be done from the
System Health screen. The Synchronization hardware OK indicator lights should be green for
both CPUs.