Alarms and events description and system troubleshooting guide

259

A

A.2.2 Commands from HMI

User With [USER ID] ID Logged
Into HMI

Indicates that the specified operator has logged
into the HMI application

User With [USER ID] ID Logged
Off HMI

Indicates that the specified operator has logged
out of the HMI application

Caution: Unable to Read HMI
Config File(elvs_config.bcf).
Defaults Loaded

The HMI was unable to load the local configuration
file from disk.

Contact GE Post Sales Service (see

How to

contact us on page 2

).

HMI Config File Loaded OK

The HMI successfully loaded the local
configuration file from disk.

Caution: Error Saving HMI
Config File

The HMI was unable to successfully store the local
configuration file to disk.

Contact GE Post Sales Service (see

How to

contact us on page 2

).

HMI Config File Saved OK

The HMI successfully loaded the local
configuration file from disk.

Switched to Entellisys LV
Lineup <LineupName>

Logged on switching to another lineup

HMI is restarted for Periodic
maintenance

The HMI has restarted itself as part of its periodic
self-maintenance routine.

Table A-2 HMI Internal Operations

Event

Description

Notes and Troubleshooting tips

Table A-3 Commands from HMI

Event

Description

Notes and Troubleshooting tips

CPU Reinitialized Issued

CPU is going to reboot, either because of a Modbus
command, or an internal issue.

The reason for the CPU reboot should be in
the event log. It will be one of the following:
CPU Reinitialize By Command, Note CPU
Internal Error 1, Note CPU Internal Error 2,
Note CPU Internal Error 3

CPU Reinitialize By Command

CPU rebooted by Modbus reset relay command

The reset relay command is issued after new
firmware or a new option string is
downloaded to the CPU.

Breaker Open Command
Received

CPU received a command via Modbus to open a
breaker

Breaker Close Command
Received

CPU received a command via Modbus to close a
breaker

Breaker Trip Command
Received

CPU received a command via Modbus to trip a
breaker

Events Cleared By Command

CPU received (via Modbus) and executed a
command to clear its event log