Alarms and events description and system troubleshooting guide

271

A

Attention Breaker Close Failed

CPU sent a close command to Messenger, but data
sent by Messenger indicates that breaker did not
close

Verify that breaker is in the Test or
Connect position.

Verify that breaker is an electric breaker.
If it is, verify that closing spring is
charged, also check the fuse for the
charging motor.

Contact GE Post Sales Service (see

How

to contact us on page 2

).

Attention Breaker Trip Failed
Shunt Trip

CPU sent a trip with shunt trip command to
Messenger, but data sent by Messenger indicates
that breaker did not open

Verify that breaker is in the Test or
Connect position.

Check shunt trip fuse.

Contact GE Post Sales Service (see

How

to contact us on page 2

).

Attention Breaker Open Failed
Flux Shifter

CPU sent an open with flux shifter command to
Messenger, but data sent by Messenger indicates
that breaker did not open

Verify that the breaker is in the Test or
Connect position.

Contact GE Post Sales Service (see

How

to contact us on page 2

).

Attention Breaker Trip Failed
Flux Shifter

CPU sent a trip with flux shifter command to
Messenger, but data sent by Messenger indicates
that breaker did not open

Verify that the breaker is in the Test or
Connect position.

Contact GE Post Sales Service (see

How

to contact us on page 2

).

Breaker Opened

Breaker has opened

Breaker Closed

Breaker has closed

Breaker Lockout

Breaker is locked out

Breaker Closing Spring Charged Breaker closing spring is charged

Breaker Primary Connected

Breaker primary is connected

Breaker Primary Disconnected

Breaker primary is disconnected

Breaker Secondary Connected

Breaker secondary is connected

Breaker Secondary
Disconnected

Breaker secondary is disconnected

Breaker Tripped

Breaker has tripped

Breaker Close Command
Rejected Breaker Locked Out

Breaker is locked out, so CPU has rejected the close
command

If breaker has a manual lockout, verify
that the lockout has been reset.

If the breaker has a network interlock, the
control logic is likely causing the breaker
to reject the close command.

Contact GE Post Sales Service (see

How

to contact us on page 2

).

Attention IO Card Detection
Mismatch Found 0 of 1

CPU expected 1 discrete I/O card, but detected
none

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Table A-8 Breaker Status Events

Event

Description

Notes and Troubleshooting tips